5.7.3
Configure access to a CSI Machinery Health Monitor
from a computer
Use a terminal emulator such as Telnet or HyperTerminal to connect to the CSI Machinery
Health Monitor using a serial cable or an ethernet cable.
(1)
Configure the settings in
in the terminal emulator's connection settings.
Prerequisites
You need a username and password to log on to a CSI Machinery Health Monitor with
Telnet.
Serial connection setup
Table 5-6:
Setting
Value
serial port
COM1
baud rate
9600
data bits
8
stop bit
1
parity
none
flow control
none
5.7.4
Boot parameters
Boot parameters
Table 5-7:
Boot parameter
Description
boot device
The device name of the system.
•
shend0 (CSI 6500 and DCMII systems)
•
cs (DCMI systems)
processor number
0
host name
The username for the FTP user.
file name
The path and filename of the firmware installed in the FTP site root
directory (C:\inetpub\ftproot, by default).
bin/6500
is the firmware for a CSI 6500.
bin/6500T
is the firmware for a CSI 6500T.
inet on ethernet (e)
IP Address and Subnet in Hex:
192.168.0.10:ffffff00
inet on backplane (b)
Intentionally blank.
host inet (h)
The IP address of the FTP server.
Example: 192.168.0.1
(1) Telnet and HyperTerminal are Windows Features that are available but are not enabled by default. You can use other terminal emulator
programs.
Software configuration
MHM-97453, Rev 1
55
Summary of Contents for Machinery Health Expert CSI 2600
Page 1: ...User Guide MHM 97453 Rev 1 April 2014 CSI 2600 Machinery Health Expert User Guide ...
Page 8: ...CSI 2600 back view Figure 2 2 Introduction to the CSI 2600 4 MHM 97453 Rev 1 ...
Page 12: ...Introduction to the CSI 2600 8 MHM 97453 Rev 1 ...
Page 26: ...Getting started 22 MHM 97453 Rev 1 ...
Page 64: ...Software configuration 60 MHM 97453 Rev 1 ...
Page 96: ...Data types 92 MHM 97453 Rev 1 ...
Page 100: ...D 2 Internal wiring diagram for the CSI 2600 ...
Page 106: ...Troubleshooting 102 MHM 97453 Rev 1 ...
Page 109: ...Index MHM 97453 Rev 1 105 ...