ADVANCED USER GUIDE
IP66/Nema 4X variable speed drive
MENU 6: PROGRAMMABLE LOGIC AND TIMERS
CONTROL TECHNIQUES
3854 en - 03.2008 / b
: Catch a spinning motor
Adjustment range : 0 to 3
Factory setting
: 0
If this parameter is enabled (
6.09
= 1 to 3), when there is a
run command or after a mains supply break, the drive
executes a procedure to calculate the motor frequency and
direction of rotation. It will automatically recalibrate the output
frequency to the measured value and reaccelerate the motor
up to the reference frequency.
• If the load is stationary at the time of the run
command or when the mains supply returns, this
operation may cause the machine to rotate in both
directions before the motor accelerates.
• Before enabling this function, check that there is
no danger to equipment and personnel.
: Enable reduced-voltage operation
Adjustment range : 0 or 1
Factory setting
: 0
0 (Disabled) (OFF): The DC bus undervoltage detection
thresholds are unchanged.
1 (Enabled) (On):Used to modify the DC bus undervoltage
detection thresholds in 400 V (voltage code 400) drives, so as
to be at the same levels as 230 V drives. This enables a 400V
(voltage code 400) rating to be supplied with 230 V if
necessary, without tripping the drive.
Note: This parameter is not active for "voltage code 200"
ratings (
6.10
is frozen at 1).
: Enable keypad FWD key
Adjustment range : 0 or 1
Factory setting
: PT version = 1
PB version = 0
0 (Disabled) (OFF): Local control FWD key disabled.
1 (Enabled) (On): Local control FWD key enabled.
: Enable keypad Stop key
Adjustment range : 0 or 1
Factory setting
: 1
0 (Disabled) (OFF): Local control Stop key disabled.
1 (Enabled) (On): Local control Stop key enabled.
If the Stop key is enabled, it is taken into account even if
control is via the terminals.
If a stop is ordered via the local console while a run command
is present, the run command on the terminals must be
opened to authorise restarting.
: Enable keypad REV key
Adjustment range : 0 or 1
Factory setting
: 0
0 (Disabled) (OFF): Local control REV key disabled.
1 (Enabled) (On): Enables the local control REV key.
: Not used
: Drive output
Adjustment range : 0 or 1
Factory setting
: 1
0 (Disabled) (diSb): Drive disabled.
1 (Enabled) (Enab): Drive enabled.
WARNING:
Disabling via the drive terminals overrides (see
8.10
)
6.15
. If the drive is enabled via the terminals, the user
can then enable or disable the drive using
6.15
.
Note:
In control via bus mode (
6.43
= 1),
6.15
is automatically set
to 0.
: Not used
: Reset energy meter
Adjustment range : 0 or 1
Factory setting
: 0
0 (Disabled) (OFF): Reset inactive.
1 (Enabled) (On): The counters
6.24
and
6.25
are reset to 0.
and
:Not used
: Powered-up time: years.days
Adjustment range : 0 to 9.364 years, days
This parameter records for how many years and days the
drive has been powered up.
: Powered-up time: hours.minutes
Adjustment range : 0 to 23.59 hrs, min
This parameter records for how many hours and minutes the
drive has been powered up.
After 23.59,
6.21
returns to 0 and
6.20
is incremented by
one day.
6.09
LCD
Display
LED
Display
Functions
0
Disabled no
Catch a spinning motor
function disabled
1
2 directions
On.2d
Enable catching of a
spinning motor rotating
clockwise or counter-
clockwise
2
Clockwise
On.Fd
Enable catching of a
spinning motor which is
rotating clockwise only
3
C/clockwise
On.rS
Enable catching of a
spinning motor which is
rotating counter-
clockwise only
6.09
6.10
6.11
6.12
6.13
6.14
6.15
6.16
6.17
6.18
6.19
6.20
6.21