ADVANCED USER GUIDE
IP66/Nema 4X variable speed drive
MENU 9: LOGIC FUNCTIONS, MOTORISED POT AND BINARY SUM
CONTROL TECHNIQUES
3854 en - 03.2008 / b
11.3 - Explanation of parameters in
menu 9
: Logic function 1 output
: Logic function 2 output
: Logic function 3 output
: Logic function 4 output
Adjustment range : 0 or 1
0 (Disabled) (OFF)
1 (Enabled) (On)
Indicate the state of the logic function outputs.
: Motorised pot output
Adjustment range : ± 100.0%
Indicates the level of the reference before scaling.
: Logic function 1 source 1
: Logic function 2 source 1
: Logic function 3 source 1
: Logic function 4 source 1
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
These parameters are used to select source 1 of the logic
functions.
Only "bit" type parameters can be used on these inputs.
If an unsuitable parameter is addressed on one of the function
1 inputs, the output will be frozen at 0.
: Logic 1 source 1 invert
: Logic 2 source 1 invert
: Logic 3 source 1 invert
: Logic 4 source 1 invert
Adjustment range : 0 or 1
Factory setting
: 0
This parameter is used to invert source 1 of the logic
functions.
0 (Disabled) (OFF): Source 1 not inverted.
1 (Enabled) (On): Source 1 inverted.
: Logic function 1 source 2
: Logic function 2 source 2
: Logic function 3 source 2
: Logic function 4 source 2
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
These parameters are used to select source 2 of the logic
functions.
Only "bit" type parameters can be used on these inputs.
If an unsuitable parameter is addressed on one of the function
1 inputs, the output will be frozen at 0.
: Logic 1 source 2 invert
: Logic 2 source 2 invert
: Logic 3 source 2 invert
: Logic 4 source 2 invert
Adjustment range : 0 or 1
Factory setting
: 0
These parameters are used to invert source 2 of the logic
functions.
0 (Disabled) (OFF): Source 2 not inverted.
1 (Enabled) (On): Source 2 inverted.
: Logic 1 output invert
: Logic 2 output invert
: Logic 3 output invert
: Logic 4 output invert
Adjustment range : 0 or 1
Factory setting
: 0
These parameters are used to invert the output of the logic
functions.
0 (Disabled) (OFF): Output not inverted.
1 (Enabled) (On): Output inverted.
and
:Not used
: Logic function 1 output destination
: Logic function 2 output destination
: Logic function 3 output destination
: Logic function 4 output destination
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
These parameters define the internal parameter which will be
assigned by the output of the logic functions.
Only unprotected "bit" type parameters can be addressed.
If an unsuitable parameter is programmed, the destination will
not be taken into account.
: Motorised pot mode
Adjustment range : 0 to 3
Factory setting
: 2
0 (Rst/ENABLE) (Rst.e): The reference is reset to 0 on each
power-up. The up/down and reset inputs are active at all
times.
1 (Prev/ENABLE) (Pre.e): On power-up, the reference is at
the same level as before power-down. The up/down and reset
inputs are active at all times.
2 (Rst/DISABLE) (Rst.d): The reference is reset to 0 on
each power-up. The up/down inputs are active only when
the drive output is active. The reset input is active at all
times.
3 (Prev/DISABLE) (Pre.d): On power-up, the reference is at the
same level as before power-down. The up/down inputs are
active only when the drive output is active. The reset input is
active at all times.
9.01
9.02
9.61
9.71
9.03
9.04
9.14
9.64
9.74
9.05
9.15
9.65
9.75
9.06
9.16
9.66
9.76
9.07
9.17
9.67
9.77
9.08
9.18
9.68
9.78
9.09
9.19
9.10
9.20
9.60
9.70
9.21