ADVANCED USER GUIDE
IP66/Nema 4X variable speed drive
MENU 10: DRIVE STATES AND DIAGNOSTICS
CONTROL TECHNIQUES
3854 en - 03.2008 / b
: Not used
: User trip 4
Adjustment range : 0 or 1
Factory setting
: 0
0 (Disabled) (OFF): The drive has not tripped.
1 (Enabled) (On): The drive trips, may or may not control
deceleration according to the configuration of
10.68
and
generates a trip code tr04.
: Not used
: Trip active at standstill
Adjustment range : 0 or 1
Factory setting
: 1
0 (Disabled) (OFF):
1 (Enabled) (On):
This parameter is used to make drive trips active at standstill.
The trips concerned are: UU, phAC , EnC1, EnC2, EnC3,
Oht2, itAC, th, CL1, CL2, CL3, Oht1.
: Trip auto-reset when
powered
Adjustment range : 0 or 1
Factory setting
: 1
0 (Disabled) (OFF):
1 (Enabled) (On):
This parameter is used to automatically reset the trip with
power "UU" applied.
to
: Not used
: LED command
Adjustment range : 0 to 1000
In the PUMP preset configuration (
11.46
= 8), this parameter
is used to control output ADI03:
-
10.90
is at 0 when
10.01
is at 1 (drive healthy).
-
10.90
is at 1000 when
10.01
is at 0 (drive tripped).
-
10.90
changes alternately from 600 to 1000 when
10.09
is at 1 (current limiting active).
: Increase number of
automatic trips
Adjustment range : 0 or 1
Factory setting
: 0
0 (Disabled) (ON)
1 (Enabled) (OFF)
This parameter is used to obtain more automatic trip resets.
When it is enabled, the maximum value of
10.34
changes
from 5 to 100.
In addition, the 10-second delay before detection of IGBT
overcurrent (OIAC) is no longer taken into account (see
10.33
). The delay is then set by
10.35
.
10.66
10.67
10.68
10.69
10.70
10.71
10.89
10.90
10.91