124
ADVANCED USER GUIDE
IP66/Nema 4X variable speed drive
MENU 16: PLC FUNCTIONS
CONTROL TECHNIQUES
3854 en - 03.2008 / b
18.3 - Explanation of parameters in
menu 16
: Timer 1 output
: Timer 2 output
: Timer 3 output
: Timer 4 output
Adjustment range : 0 or 1
0 (Disabled) (OFF)
1 (Enabled) (On)
These parameters indicate the state of the timer relay
outputs.
: Timer 1 source
: Timer 2 source
: Timer 3 source
: Timer 4 source
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
These parameters are used to select the source for the timer
relay inputs.
Only "bit" type parameters can be assigned to these inputs. If
an unsuitable parameter is addressed on an input, the input
will be frozen at 0.
: Timer 1 mode select
: Timer 2 mode select
: Timer 3 mode select
: Timer 4 mode select
Adjustment range : 0 or 1
Factory setting
: 0
0 (ON timer) (On): The relay is used for on-delay timing.
The output changing to 1 is delayed in relation to the
input changing to 1.
1 (OFF timer) (OFF): The relay is used for off-delay timing.
The output changing to 0 is delayed in relation to the input
changing to 0.
: Timer 1 unit
: Timer 2 unit
: Timer 3 unit
: Timer 4 unit
Adjustment range : 0 to 2
Factory setting
: 0
0 (Second) (Sec): The unit of time for the timer relay is the
second.
1 (Minute) (Min): The unit of time for the timer relay is the
minute.
2 (Hour) (hour): The unit of time for the timer relay is the
hour.
: Timer 1 value
: Timer 2 value
: Timer 3 value
: Timer 4 value
Adjustment range : 0 to 60.0
Factory setting
: 0
These parameters are used to set the timer delay periods.
The unit depends on the configuration of
16.04
,
16.14
,
16.24
and
16.34
.
to
: Not used
: Timer 1 output destination
: Timer 2 output destination
: Timer 3 output destination
: Timer 4 output destination
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
These parameters are used to select the destination for the
timer relay outputs.
Only "bit" type parameters can be assigned to these outputs.
If an unsuitable parameter is addressed on an output, the
output will be frozen at 0.
: Timer 1 inverted output state
: Timer 2 inverted output state
: Timer 3 inverted output state
: Timer 4 inverted output state
Adjustment range : 0 or 1
0 (Disabled) (OFF)
1 (Enabled) (On)
These parameters indicate the state of the inverted output of
the timer relays.
to : Not
used
to
to
: Latch 1 output
: Latch 2 output
: Latch 3 output
: Latch 4 output
Adjustment range : 0 or 1
These parameters indicate the state of the latching relay
outputs.
16.01
16.11
16.21
16.31
16.02
16.12
16.22
16.32
16.03
16.13
16.23
16.33
16.04
16.14
16.24
16.34
16.05
16.15
16.25
16.35
16.06
16.08
16.09
16.19
16.29
16.39
16.10
16.20
16.30
16.40
16.16
16.18
16.26
16.28
16.36
16.38
16.41
16.51
16.61
16.71