ADVANCED USER GUIDE
IP66/Nema 4X variable speed drive
MENU 11: SERIAL LINK - DRIVE CHARACTERISTICS - MISCELLANEOUS
CONTROL TECHNIQUES
3854 en - 03.2008 / b
: Selection of preset configuration
Adjustment range : 0 to 13
Factory setting
: PT version = 11
other = 0
Used to select a configuration which automatically assigns the I/O and defines parameters
11
to
24
of menu 0.
Note: Modifications to
11.46
must be made with the drive disabled.
11.46
is stored permanently. If one of the relevant parameters is modified by the user after automatic configuration,
11.46
automatically switches to mode 13 (OPEn).
0 (0-10V/4-20mA) (A1.A2)
: A current reference input and a voltage reference input selectable via
digital input.
1 (0-10V/3Pr) (A1.Pr)
: One voltage reference input and 3 preset references, selectable via 2 digital inputs.
2 (4-20mA/3Pr) (A1.Pr)
: One current reference input and 3 preset references, selectable via 2 digital inputs.
3 (4 Preset ref) (4Pr)
: 4 preset references, selectable via 2 logic inputs.
4 (8 Preset ref) (8Pr)
: 8 preset references, selectable via 3 logic inputs.
5 (Motorised pot.) (E.Pot)
: Motorised potentiometer (up, down).
6 (Torque ctrl) (Torq)
: Speed or torque control with speed limiting.
7 (PID CTRL) (Pid)
: PID control.
8 (Pumps&Vent.) (PUMP)
: Pump regulation.
9 (ANALOG/PTC (ACtP)
: A voltage or current reference and a PTC sensor input.
10 (HOIST CONTROL) (HoiS): control of travelling crane.
11 (KEYPAD CTRL) (Pad)
: Local control via the keypad.
12 (AUTO/MANUAL) (HuAC): Auto/manual mode.
13 (Open) (OPEn)
: No configuration, parameter-setting mode is open.
Note: Modification of certain parameters in menu 0 automatically causes
11.46
to change to "OPEn" (open parameter setting).
This may result in modification of the wiring diagram for the selected preset configuration.
: Display duration in alternating mode
Adjustment range : 0 to 250 s
Factory setting
: 5 s
In alternating display mode,
11.22
= 2, used to define for
how long each value is displayed.
: Last preset configuration
Adjustment range : 0 to 12
0 (0-10V/4-20mA) (A1.A2)
1 (0-10V/3Pr) (A1.Pr)
2 (4-20mA/3Pr) (A2.Pr)
3 (4 Preset ref) (4Pr)
4 (8 Preset ref) (8Pr)
5 (Motorised pot.) (E.Pot)
6 (Torque ctrl) (Torq)
7 (PID CTRL) (Pid)
8 (Pumps&Vent.) (PUMP)
9 (ANALOG/PTC (ACtP)
10 (HOIST CONTROL) (HoiS)
11 (KEYPAD CTRL) (Pad)
12 (AUTO/MANUAL) (HuAC)
This parameter stores and indicates the last preset
configuration selected by
11.46
. Value 13 (OPEn) is not
taken into account.
: Parameter displayed at power-up
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
This parameter is used to select the parameter to be
displayed at power-up (see
11.22
).
to
: Not used
Menu 0
Preset configurations
0
1
2
3
4
5
6
7
8
9
10
11
12
13
(A1.A2) (A1.Pr) (A2.Pr)
(4Pr)
(8Pr)
(E.Pot) (Torq)
(Pid) (PUMP) (ACtP) (HoiS)
(Pad) (HuAC) (OPEn)
11
7.06
7.06
7.06
1.21
1.21
7.06
7.06
7.06
7.06
-
-
1.51
-
-
12
7.11
1.22
1.22
1.22
1.22
9.28
7.11
7.11
7.11
-
1.22
1.21
7.11
-
13
-
1.23
1.23
1.23
1.23
9.21
-
14.10 14.10
-
-
6.11
-
-
14
-
1.24
1.24
1.24
1.24
9.22
-
14.11 14.11
-
-
6.12
-
-
15
-
-
-
-
1.25
9.23
-
14.12 14.56
-
-
6.13
-
-
16
-
-
-
-
1.26
9.24
-
14.13 12.04
-
-
-
-
-
17
-
-
-
-
1.27
9.03
-
14.14 16.05
-
-
-
-
-
18
-
-
-
-
1.28
-
-
14.15 14.51
-
-
-
-
-
19
-
-
-
-
-
-
7.12
7.12 14.53
-
-
-
-
-
20
-
-
-
-
-
-
-
7.16 14.54
-
-
-
-
-
21
-
-
-
-
-
-
-
14.20 14.55
-
-
-
-
-
22
-
-
-
-
-
-
-
14.21 5.04
-
-
-
-
-
23
-
-
-
-
-
-
-
14.19 16.38
-
-
-
-
-
24
-
-
-
-
-
-
-
14.01 16.28
-
-
-
-
-
11.46
11.47
11.48
11.49
11.50
11.58