35
Automatic settings
Control System KNX WS1000 Color
• Status: 18.04.2016 • Errors excepted. Subject to technical changes.
row keys, specify the slat position in % (0% = closed, 50% = horizontal, 100% = closed).
Default setting: 75% (slightly open).
Tracking the position of the sun: If the slats should be opened in accordance with the
position of the sun, press the button so it changes to Yes. You can adjust the slat open-
ing for the various angles of the sun. For this use the arrow keys next to the % details.
Default setting: 0° to 15°: 100% (closed), 15° to 30°: 80%, 30° to 45°: 65%, 45° to 90°: 50%
(horizontal).
Confirm your setting with the
OK
button.
Press the button to select the indoor sensor the control system will use for these blinds
respectively shutters (Pre-setting: first sensor in the list). As long as “
No Sensor
” is
selected, the indoor temperature will not be taken into account by the control system
for this shade.
Confirm your setting with the
OK
button.
Press the button to set the indoor temperature block. Until an indoor sensor is selected,
the indoor temperature block will not be active.
The interior blocking temperature enables the use of solar energy to warm the room.
When the indoor temperature is below the set value, e.g. in the morning, the shading
will remain retracted despite the sunshine.
As soon as the set indoor temperature is exceeded, the block is released and the shade
is activated.
When the indoor temperature drops once again, the block is reactivated when the tem-
perature drops below the pre-set value by more than 3.0°C (hysteresis). Note that the
shade only retracts once the retraction delay time has elapsed.
System > Automatic Settings > General Settings > Movement Delays
3.3. Adjust movement delays (shading)
Set temperature: With the arrow keys, adjust the value for the desired room tempera-
ture. Default setting: 25.0 °C.
Disable block: If the blinds respectively shutters should be deployed to offer shade re-
gardless of the indoor temperature, press the
Off
button.
Confirm your setting with the
OK
button.
Press the button to enable or disable the closing of the blind respectively the roller
shutter at night.
Sensor Selection
Indoor Temp.
Night Closure