48
Automatic settings
Control System KNX WS1000 Color
• Status: 18.04.2016 • Errors excepted. Subject to technical changes.
Air Supply Unit WFL, ventioaltor at multifunctional output or RF Relay: The ventilation
unit is opened as soon as the temperature exceeds the set value. It is closed again as
soon as the temerature drops more than 2.0°C below the set value (hysteresis).
Shutting off ventilation: If ventilation is to be independent of indoor temperature, press
the button labelled
OFF
.
Confirm your setting with the
OK
button.
Press the button to set the air humidity above which the ventilation will be switched on
at night. Until an indoor sensor is selected, the air humidity will be disregarded.
Setting humidity: Adjust the value for the desired humidity using the arrow buttons.
Pre-setting: 80%.
Shutting off ventilation: If ventilation is to be independent of air humidity, press the
button labelled
OFF
.
Confirm your setting with the
OK
button.
Press the button to set the supply air temperature block (summer operation). With WFL
supply air units, the supply air temperature is recorded by a thermometer integrated
into the WFL. With devices from other manufacturers the outdoor temperature at the
weather station is used as the supply air temperature.
Enable: If the supply air unit should be closed when the supply air temperature is
warmer than the room temperature, select
Yes
.
Disable: If the supply air unit should also then be/remain open when the supply air tem-
perature is warmer than the room temperature, select
No
(default setting).
Confirm your setting with the
OK
button.
Press the button to set the ventilation levels of the motorised roof ventilators. The fur-
ther the indoor temperature and air humidity lie above the reference values, the higher
the ventilator shifts.
Use the arrow buttons to change the start and maximum values according to your
wishes. Default setting: Start with level 1, maximum level 8 (full level utilisation).
Confirm your setting with the
OK
button.
Air Humidity
For all ventilation units.
Humidity Ventil.
Supply-Air Temp.
Only for WFL and ventilation units at RF Relay.
Exhaus Air Levels
Only for WL610/WL305 and
air supply on RF-VM.
Ventilation Levels