60
Automatic settings
Control System KNX WS1000 Color
• Status: 18.04.2016 • Errors excepted. Subject to technical changes.
Start / end:
Set the start and end of the time period by selecting each hour and minute field con-
secutively and setting the time using the arrow keys.
Weekdays:
Select the day of the week on which the time period should be activated. More than
one day can also be selected.
Confirm your setting with the
OK
button.
3.2.4. Adjust ventilation block
As soon as a cooling/air-conditioning unit is activated, windows will be closed and
ventilators switched off. If the cooling is switched off again, the ventilation will stay off
for a while, to prevent the cooled air to be discharged immidiately through windows
or ventilation units. You can adjust the delay time for this.
The ventilation block is also iniciated by devices that are connected to the multifunc-
tion input as climate signallers.
The ventilation block settings can be accessed by pressing the buttons:
Use the arrow keys to set how many minutes ventilation via windows or ventilators
should remain blocked after an air-conditioning device is switched off.
Default setting: 120 minutes.
Confirm your setting with the
OK
button.
3.2.5. Set night-time re-cooling (ventilation)
The night-time re-cooling function using the windows and ventilation equipment is ac-
tivated once a set outdoor temperature is exceeded for an extended period of time.
The weather data display (Start screen) then shows “Night-time re-cooling” next to the
outdoor temperature value. The display can also show “Frost alarm” and “Window
movement limitation” in turn.
2.1. Weather data display (start screen)
The window(s) and ventilator(s) which are used for night-time re-cooling as well as the
time period over which these are activated can be set in the automatic operation func-
tions for the individual windows and ventilators.
Automatic
Settings
Ventilation Block
System
General
Settings