82
Instruction Manual IM02602008E - Rev. D
Transformer Temperature Controllers
IM02602008E - Rev. D May 2019 www.eaton.com
Modbus Table 4 - Modbus Configurations (Cont’d)
Function
Code
Register
Address
(Decimal)
Register
Address
(Hex)
Register Type
Parameter Description
Data Range
Number
of Bytes
3/6/16
40105 ‡
69
Read/Write
Modbus Parity
0 – None
1 – Even
2 – Odd
2
3/6/16
40106 ‡
6A
Read/Write
Modbus Stop Bits
1 – One
2 – Two
2
3/6/16
40107 ‡
6B
Read/Write
Modbus Address
1 – 247
2
3/6/16
40108
6C
Read/Write
Active Channels
bit 0 = 1 = Activate Input 1
bit 1 = 1 = Activate Input 2
bit 2 = 1 = Activate Input 3
bit 3 = 1 = Activate Input 4
2
3/6/16
40109
6D
Read/Write
Channel Display Setting
0 – ABC
1 – UVW
2 – 123
2
3/6/16
40110
6E
Read/Write
Thermocouple Type
0 – K
1 – E
2
3/6/16
40111
6F
Read/Write
Reverse Detection
0 – OFF
1 – ON
2
3/6/16
40112
70
Read/Write
FAN 1 Setpoint in
Fahrenheit
32 – 482, OFF(0x0FFF)
2
3/6/16
40113
71
Read/Write
FAN 2 Setpoint in
Fahrenheit
32 – 482, OFF(0x0FFF)
2
3/6/16
40114
72
Read/Write
FAN DeadBand in
Fahrenheit
41 – 122
2
3/6/16
40115
73
Read/Write
Number to activate Fan 1
1-Any 1,
2-Any 2,
3-All
2
3/6/16
40116
74
Read/Write
Number to activate Fan 2
1-Any 1,
2-Any 2,
3-All
2
3/6/16
40117
75
Read/Write
FAN 1 Wear Setting
1-65000 †
2
3/6/16
40118
76
Read/Write
FAN 2 Wear Setting
1-65000 †
2
3/6/16
40119
77
Read/Write
FAN Mode Control
1 = Auto
2 = Manual
3 = Auto-Manual
2
3/6/16
40120
78
Read/Write
FAN Exercise Cycle Time
(0.01-30)*100, OFF(0x0FFF)
2
3/6/16
40121
79
Read/Write
FAN Exercise Run Time
1-120
2
3/6/16
40122
7A
Read/Write
Alarm Setpoint in
Fahrenheit
32 – 482, OFF(0x0FFF)
2
3/6/16
40123
7B
Read/Write
Alarm DeadBand in
Fahrenheit
41 – 68
2