40
Instruction Manual IM02602008E - Rev. D
Transformer Temperature Controllers
IM02602008E - Rev. D May 2019 www.eaton.com
1. Select the Modbus parameters desired, as follows:
Baud Rate
sets the baud rate desired. The options are
9600
,
19200
, or
38400
. The default is
9600
.
Parity
sets the parity desired. The options are
Odd
,
Even
and
None
. The
default is
None
.
Stopbits
sets the stopbit desired. The options are
One
or
Two
. The default is
Two
.
Modbus Address
sets the Modbus address desired, from
1- 247
. The default
is
1
.
2. Click the
To Device
check box to save this setting to the TC device when the
Write
function is selected.
3. Click
Next
or
Previous
, or use the mouse, to select another configura-
tion category.
4. When all configuration parameters have been changed/selected click
Write
to save all selected parameters to the TC device, or click
Save
or
Save As
to store this configuration as a file on the laptop for later use.
4.2.4.1.6 Trend Data Interval (TC-100 Only)
Select
Trend Data Interval
. The Trend Data Interval configuration parameters
will appear.
1. Select the Trend time interval for logging trend data or disabling the logging
of data, as follows.
Trend Time Setting
sets the time period desired. The options are
Off
,
Minutes
,
Hours
, or
Days
. The default is
Hours
.
Trend Time Increment Settings
sets the tie interval desired for logging
trend data. The options range and default change based on the previous Trend
Time Setting.
For
Minutes
, the range is
1-60
and the default is
30
.
For
Hours
the range is
1-24
and the default is
12
.
For
Days
the range is
1-30
and the default is
1
.
If the Trend Time Setting is
Off
, no trend data will be recorded and there will
be no option for Trend Time Increment Settings. are
1-60
. The default is
12
(Hours).
2. Click the
To Device
check box to save this setting to the TC-100 when the
Write
function is selected.
3. Click
Next
or
Previous
, or use the mouse, to select another configura-
tion category.
4. When all configuration parameters have been changed/selected click
Write
to save all selected parameters to the TC-100, or click
Save
or
Save As
to store this configuration as a file on the laptop for later use.