Instruction Manual IM02602008E - Rev. D
Transformer Temperature Controllers
IM02602008E - Rev. D May 2019 www.eaton.com
Modbus Table 4 - Modbus Configurations (Cont’d)
Function
Code
Register
Address
(Decimal)
Register
Address
(Hex)
Register Type
Parameter Description
Data Range
Number
of Bytes
3/6/16
40124
7C
Read/Write
Alarm Fail Safe
0 = OFF
1 = ON
2
3/6/16
40125
7D
Read/Write
Alarm Latch
0 = OFF
1 = ON
2
3/6/16
40126
7E
Read/Write
Alarm Display
0 = OFF
1 = ON
2
3/6/16
40127
7F
Read/Write
Trip Setpoint in Fahrenheit
32 – 482, OFF(0x0FFF)
2
3/6/16
40128
80
Read/Write
Trip DeadBand in
Fahrenheit
41 – 68
2
3/6/16
40129
81
Read/Write
Trip Fail Safe
0 = OFF
1 = ON
2
3/6/16
40130
82
Read/Write
Trip Latch
0 = OFF
1 = ON
2
3/6/16
40131
83
Read/Write
Buzzer
0 = OFF
1 = Trigger on Alarm
2 = Trigger on Trip
3 = Any
2
3/6/16
40132
84
Read/Write
Buzzer Tone
0 – Intermittent
1 = Continuous
2
3/6/16
40133
85
Read/Write
Trend Time Unit
0 – Off †
1 – Minutes †
2 – Hours †
3 – Days †
2
3/6/16
40134
86
Read/Write
Trend time Value
0-60 †
2
3/6/16
40135
87
Read/Write
Discrete Input 1 Selection
0 – Not Used †
1 – Fan Fail †
2 – User Defined †
2
3/6/16
40136
88
Read/Write
Discrete Input 1 Edge
0 – Not Applicable †
1 – Open †
2 – Close †
3 – Direct4 – Invert †
2
3/6/16
40137
89
Read/Write
Discrete Input 1 Effect
0 – Not Applicable †
1 – Alarm Only †
2 – Alarm + Fan1 †
3 – Alarm + Fan2 †
4 – Alarm †
5 – Trip †
6 – Fan2 †
7 – Fans ON †
8 – Fans OFF †
2