47
Instruction Manual IM02602008E - Rev. D
Transformer Temperature Controllers
IM02602008E - Rev. D May 2019 www.eaton.com
Discrete Input 2 Selectione:
Configures the use of Discrete Input 2. The
options are
Not Used
,
Fan Fail
, and User
Defined
.
Fan Fail
may be used with an airflow sensor or micro switch connected to
ventilation louvers to indicate when the fan is operating properly.
User Defined
may be used with a wider array of external sensors or
switches to generate an alarm or trip condition, control the fans, or even
control other equipment using the Fan2 relay
Default is
Not Used
.
Discrete Input 2 Edgee:
This option should only be set after the Discrete
Input 2 Selection is changed from
Not Used
. The options differ depend-
ing on the Discrete Input 2 Selection.
For
Fan Fail
the options are
Open
or
Closed
and configure the input
state that indicates a fan failure. This allows connection to either normally
closed or normally open contacts. The default is
Open
.
For
User Defined
two options are given to define the relationship
between the input state and output state. The options are
Direct
, which
means a closure on the input results in a closure on the output, or
Invert
which means an open on the input causes a closure on the output. This
allows the use of normally open or normally closed contacts on the input.
The default is
Direct
.
Discrete Input 2 Effecte:
This option should only be set after the Discrete
Input 2 Selection is changed from
Not Used
. The options differ depending
on the Discrete Input 2 Selection.
For
Fan Fail
the options are
Alarm Only
or
Alarm + Fan 1
. The default is
Alarm Only
. Selecting either option will activate an alarm condition when
a fan failure is detected, activating the alarm relay and front panel LED,
and if enabled displaying
A. AIR-ND
(airflow not detected). The second
option can be used to configure Fan 2 as a backup to come on if FAN 1
fails.
For
User Defined
the options are
Alarm
,
Trip
,
Fan2
,
Fans ON
, and
Fans
OFF
. The default is
Alarm
. The Fans ON and Fans OFF control both fans
and override temperature setpoints, thus they can be used to always force
fans On or Off.
2. Click the
To Device
check box to save this setting to the TC-100 when the
Write
function is selected. change.
3. Click
Next
or
Previous
, or use the mouse, to select another param-
eter.
4. When all configuration parameters have been changed/selected click
Write
to save all selected parameters to the TC-100, or click
Save
or
Save As
to store this configuration as a file on the laptop for later use.