76
Instruction Manual IM02602008E - Rev. D
Transformer Temperature Controllers
IM02602008E - Rev. D May 2019 www.eaton.com
Description Specification
EMC
Immunity
- ANSI/IEEE C37.90.1-2002 - Standard Surge Withstand Capability (SWC) Tests for Protective Relays and Relay
Systems
- ANSI/IEEE C37.90.2-2004, Standard Withstand Capability of Relay Systems to Radiated Electromagnetic
Interference from Transceivers.
- EN 61000-4-2 ESD
- EN 61000-4-3 RF Radiated Immunity
- EN 61000-4-4 EFT/Burst Immunity
- EN 61000-4-5 Surge Immunity
- EN 61000-4-6 RF Conducted Immunity
- EN 61000-4-8 Power Frequency Magnetic Field Immunity
- EN 61000-4-11 Voltage Variation Immunity
Emissions
- EN 50011 CISPR-11, Class A
- CFR 47 FCC Part 15 Subpart B Class A
Clock
Accuracy
+/- 1 minute/month @ 25º C
Backup
30 days with no control power
Logging
Trend Data †
100 entries, logging interval programmable from 1 minute to 30 days
Alarm Events †
Last 25 alarm events
Trip Events †
Last 25 trip events
Maximum Temperature (All models)
Maximum instantaneous temperature stored for each channel (resettable from front panel)
Fan Wear †
Total Hours ON, Maximum Continuous Hours ON for each Fan Output. (resettable from front panel)
Memory Retention (All models)
40 years (with no power)
Mechanical (in Barrier Cabinet)
Dimensions (HxWxD)
38.4 cm x 22.4 cm x 10.9 cm (15.12” x 8.82” x 4.28”)
Weight
9.7 lbs.
Approvals
Underwriters Laboratories
UL-873 Temperature-Indicating and Regulating Equipment
Canadian Standards Association
C22.2 No. 24-93 Temperature-Indicating and Regulating Equipment
† = TC-100 Only