79
Instruction Manual IM02602008E - Rev. D
Transformer Temperature Controllers
IM02602008E - Rev. D May 2019 www.eaton.com
Parameter Name
Front Panel Display Name
Default Value
Range
Description
Trend Time Increment Setting † TREND/HOUR (MINUTES or DAY)
12
1-60(minutes)1-
24(hours)1-30(days)
Sets the time interval for logging trend
data.
Discrete Input 1 Selection †
D-INPUT1/
Not Used
Not Used/Fan Fail/User
Defined
Configures use of discrete input 1
Discrete Input 1 Edge †
D-INPUT1/
Not Applicable
Varies with use, needs further explanation
Discrete Input 1 Effect †
D-INPUT1/
Not Applicable
Varies with use, needs further explanation
Discrete Input 2 Selection †
D-INPUT2/
Not Used
Not Used/Fan Fail/User
Defined
Configures use of discrete input 2
Discrete Input 2 Edge †
D-INPUT2/
Not Applicable
Varies with use, needs further explanation
Discrete Input 2 Effect †
D-INPUT2/
Not Applicable
Varies with use, needs further explanation
Year
TIME.DATE/DATE/YEAR
2009
2000-3000
Set the current year for alarm and trip his-
tory and trend logging.
Month
TIME.DATE/DATE/MONTH
1
1-12
Set the current month for alarm and trip
history and trend logging.
Day
TIME.DATE/DATE/DAY
1
1-31
Set the current day for alarm and trip his-
tory and trend logging.
Hours
TIME.DATE/TIME/HOUR
1
1-24
Set the current hour for alarm and trip his-
tory and trend logging.
Minutes
TIME.DATE/TIME/MINUTES
1
1-60
Set the current minute for alarm and trip
history and trend logging.
Change Password
CHW-PWD
0000
0000-FFFF
Change the password.
† = TC-100 Only
‡ = TC-50 Modbus and TC-100
Programming Table 3 – Test functions.
Parameter Name
Front Panel Display Name
Description
Test Relays
T-RELAY
Tests the two fan relays and the alarm and trip
relays by allowing the user to raise the tempera-
ture above the programmed setpoint. Press Back
to return to the previous menu.
Internal Temperature
T-INT
Displays the internal unit temperature. Press Back
to return to the Test menu.
Test Display
T-DISP
Lights up all segments of the 8-character display.
Displays TEST OVR when done. Press Back to
return to the Test menu.
Test Buttons
T-BUTTON
Displays the button name of each button pressed.
Press Test button again to return to the test menu.
Test LEDs
T-LED
Lights all LEDs for several seconds. Displays TEST
OVR when done. Press Back to return to the Test
menu.