61
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.2.12.3
495
Adjust maximum “adjust maximum”
These parameters define the minimum and maximum of adjusted signals.
Reference [Hz]
Ajust Max 10 %
Ajust Min 10 %
Adjust input
Input Reference [Hz]
27,5 Hz
25,0 Hz
22,5 Hz
If minimum and maximum are not equal to zero adjustment is not at the middle point
of analog input or at zero point if -10...+10 Vdc input is used. Below picture minimum is
20 % and maximum 10 %.
Adjustment
10 %
50 %
100 %
Adjust
Input [%]
66,66
20 %
5.3 Ramp control
SEL
G
IN 0
IN 1
R
Final Ramp Time
P
Ramp time 1
P
Ramp time 2
DI
Ramp time 1/2
SEL
G
IN 0
IN 1
DI
Inching Active
P
Inching Ramp
MULDIV
VALUE
MULTIP
DIVIS
F
Ramp Reduction
P
100 %
SEL
G
IN 0
IN 1
MULDIV
VALUE
MULTIP
DIVIS
F
Prohibited area
P
1,0
P
Prohibited Factor
SEL
G
IN 0
IN 1
F
Ramp Follower
P
0,0 s