SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
4. SPX Advanced application – parameter list
4.1 Basic parameters
Table 1 . Basic parameters G1 .1
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.1.1
Minimum frequency
0.00
P1.1.2
Hz
0.00
101
P1.1.2
Maximum frequency
P1.1.1
320.00
Hz
60.00
102
Note:
If fmax > than the motor synchronous speed, check suitability for
motor and drive system
P1.1.3
Motor nominal voltage
180
690
V
2: 230V
4: 480V
5: 690V
110
Check the rating plate of the motor. Note also used connection Delta/Star
P1.1.4
Motor nominal frequency
8.00
320.00
Hz
60.00
111
Check the rating plate of the motor
P1.1.5
Motor nominal speed
5
20 000
rpm
1725
112
The default applies for a 4-pole motor and a nominal size frequency
converter.
P1.1.6
Motor nominal current
0.1 x I
H
2 x I
H
A
I
H
113
Check the rating plate of the motor.
P1.1.7
Motor power factor
0.30
1.00
0.85
120
Check the rating plate of the motor
P1.1.8
Motor nominal power
0.0
3200.0
kW
0.0
116
Check the rating plate of the motor
P1.1.9
Magnetizing current
0.00
100.00
A
0.00
612
0.00 A = Drive uses estimated value from motor name plate values
P1.1.10
Identification
0
4
0
631
0=No action
1=Identification w/o run
2=Identification with run
3=Encoder ID Run
4=Ident All
5=Absolute encoder, locked rotor
Note:
Set motor control mode to freq control before identification!
P1.1.11
Motor type
0
1
0
650
0=Induction Motor
1=PMS Motor
P1.1.12
Local control source
0
3
0
172
0=Keypad
1=I/O Term
2=I/O Term B
3=Fieldbus
P1.1.13
Remote 1 control source
0
3
1
173
See P1.1.12
P1.1.14
Remote 2 control source
0
3
3
174
See P1.1.12
4.2 Reference handling
4.2.1 Basic settings
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.2.1
Local reference
0
17
8
121
0=AI1
1=AI2
2=AI1+AI2
3=AI1-AI2
4=AI2-AI1
5=AI1xAI2
6=AI1 Joystick
7=AI2 Joystick
8=Keypad
9=Fieldbus
10=Motor potentiometer
11=AI1, AI2 minimum
13=Max frequency
14=AI1/AI2 selection
15=Encoder 1
16=Encoder 2
17=PID Output