SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.5.1.26
455
Fieldbus input data 1 “FB dig input 1”
P1.5.1.27
456
Fieldbus input data 2 “FB dig input 2”
P1.5.1.28
459
Fieldbus input data 3 “FB dig input 3”
P1.5.1.29
169
Fieldbus input data 4 “FB dig input 4”
P1.5.1.30
170
Fieldbus input data 5 “FB dig input 5”
The data from the Fieldbus main control word can be led to the drive’s digital outputs.
See used fieldbus board manual for location of these bits.
P1.5.1.31
756
Safe disable active “safe disable act”
Select the digital output to show the status of the Safe Torque Off.
P1.5.1.32
458
Charge switch state “charge switch”
Closed when the DC bus has passed the pre-charge complete threshold voltage
Code
ID
Parameter
Notes
P1.5.2.1
464
Analog output 1 signal selection “Iout 1 signal”
P1.5.3.1
471
Analog output 2 signal selection “Iout 2 signal”
P1.5.4.1
478
Analog output 3, signal selection “Iout 3 signal”
P1.5.5.1
1527
Analog output 4, signal selection “Iout 4 signal”
Connect the AO1 signal to the analog output of your choice with this parameter.
P1.5.2.2
307
Analog output function “Iout content”
P1.5.3.2
472
Analog output 2 function “Iout 2 content”
P1.5.3.2
479
Analog output 3, function “Iout 3 content”
P1.5.3.2
1520
Analog output 4, function “Iout 4 content”
This parameter selects the desired function for the analog output signal.
0 “Not used”
Analog output is forced to 20 % (= 2 V/4 mA)
1 “O/P Freq” – Drive Output Frequency
Output frequency from zero to maximum frequency.
2 “Freq Ref” -
Freq. reference from zero to maximum frequency
3 “Motor speed “
Motor speed from zero speed to motor synchronous speed
4 “O/P Current” – Drive Output Current
Drive output current from zero to motor nominal current
5 “Motor Torque “
Motor torque from zero to motor nominal torque (100 %)
6 “Motor Power”
Motor power from zero to motor nominal power (100 %)
7 “Mot Voltage”
Drive output voltage from zero to motor nominal voltage
8 ”DC-link volt”
500 V unit: DC voltage from zero to 1000 Vdc
690 V unit: DC voltage from zero to 1317 Vdc
9 “AI1”
Unfiltered Analog input 1 signal
10 “AI2”
Unfiltered Analog input 2 signal
11 “Fout,min-max”
Output frequency from minimum frequency to maximum frequency
5.5.1.2 Fieldbus digital inputs connection
5.5.2 Analog outputs 1 & 2 & 3 & 4