92
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.6.2.1
1722
Power limit “Power limit”
General power limit for both motoring and generator side. This value is the final limit
for all scaling functions. This value should not be used for scaling but for the maximum
safety limit because the ramp up rate function is ineffective when this parameter is
changed.
P1.6.2.2
1290
Generator power limit “GenerPowerLimit”
Generator side power limit. This limit value is used for all scaling functions and power
limit ramp rate functions.
P1.6.2.3
1289
Motoring power limit “MotorPowerLimit”
Motoring side power limit. This limit value is used for all scaling functions and power
limit ramp rate functions.
P1.6.2.4
1513
Generator power limit 1 “Gen.PowerLimit 2”
Generator side power limit values when limits are activated by digital inputs. When
both digital inputs are activated the power limit is forced to zero.
P1.6.2.6
1503
Motoring power limit 1 “Mot.PowerLimit 1”
P1.6.2.7
1504
Motoring power limit 2 “Mot.PowerLimit 2”
Motoring side power limit values when limits are activated by digital inputs. When
both digital inputs are activated the power limit is forced to zero.
DI
Motoring power limit 1
B0
IN00
IN01
IN10
IN11
B1
SEL4
Limit for ramping control
Motoring power limit 2
Motoring power limit
Motoring power limit 1
Motoring power limit 2
Power limit zero
DI
P
P
P
F
P1.6.2.8
1502
Power limit increase rate “PowerLimInc.rate”
Defines the power limit increase rate. Decreasing power limit will be in effect
immediately.
Power Limit
80 %
Input Limit
Internal Limit
10 % / s
20 %
6 s