18
SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.2.9.4 Torque reference filtering
time
0
32000
ms
0
1244
P1.2.9.5 Torque reference dead zone
0.0
300.0
%
0.00
1246
P1.2.9.6 Torque Select
0
5
2
1278
0=Speed control
1=Maximum freq limit
2=Ramp output
3=Min
4=Max
5=Window
P1.2.9.7 Window negative
0.00
50.00
Hz
2.00
1305
P1.2.9.8 Window positive
0.00
50.00
Hz
2.00
1304
P1.2.9.9 Window negative off
0.00
P1.10.11 Hz
0.00
1307
P1.2.9.10 Window positive off
0.00
P1.10.12 Hz
0.00
1306
P1.2.9.11 Torque step
–100.0
100.0
0.0
0.0
1253
4.2.5 Torque reference OL settings
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.2.9.11.1 Open loop torque control
minimum frequency
0.00
50.00
Hz
3.00
636
P1.2.9.11.2 Open loop torque controller
P gain
0
32000
150
639
P1.2.9.11.3 Open loop torque controller
I gain
0
32000
10
640
4.2.6 Prohibit frequency parameters
Table 3 . Prohibit frequencies G1 .2 .10
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.2.10.1 Prohibit frequency range
1 low limit
–1.00
320.00
Hz
0.00
509
0=Not used
P1.2.10.2 Prohibit frequency range
1 high limit
0.00
320.00
Hz
0.00
510
0=Not used
P1.2.10.3 Ramp time factor
0.1
10.0
x
1.0
518
Multiplier of the currently
Selected ramp time between prohibit frequency limits.
4.2.7 Motor potentiometer
Table 4 . Motor potentiometer (G1 .5)
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.2.11.1 Motor potentiometer
ramp rate
0.10
2000.00
Hz/s
1.00
331
Ramp rate for motor potentiometer
P1.2.11.2 Motor potentiometer
frequency reference
memory reset
0
2
1
367
0=No reset
1=Reset in stop state
2=Reset in powered down
P1.2.11.3 Motor potentiometer
reference copy
0
2
0
366
0=No copy
1=Copy Reference
2=Copy output frequency