156
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
5.18.3 Feedbacks
Code
ID
Description
Notes
R1.17.2.4
Keypad PID reference 1
Keypad PID set point 1
P1.17.2.5
361
Keypad PID set point 1 minimum “PID SP1 min”
This allows the range of keypad set point 1 to be limited
P1.17.2.6
362
Keypad PID set point 1 maximum “PID SP1 max”
This allows the range of keypad set point 1 to be limited
R1.17.2.7
Keypad PID reference 2
Keypad PID set point 2
P1.17.2.8
363
Keypad PID set point 2 minimum “PID SP2 min”
This allows the range of keypad set point 2 to be limited
P1.17.2.9
364
Keypad PID set point 2 maximum “PID SP2 max”
This allows the range of keypad set point 2 to be limited
P1.17.2.10
364
PID reference rise time “PID ref rise time”
This determines the rate of change of a rising PID set point
P1.17.2.11
344
PID reference fall time “PID ref fall time”
This determines the rate of change of a falling PID set point
P1.17.2.12
376
PID sum point reference“PID sumpoint ref”
This source is added to the PID output
Code
ID
Description
Notes
P1.17.3.1
333
Feedback function “function”
This parameter determines the source of the PID controllerFeedback value. This allows
for selection between 2 sourcesor math functions between 2 sources.
P1.17.3.2
334
PID source 1 select“source 1 sel”
This sets the source of the source 1 set point value this can come from an analog input,
keypad, or fieldbus.
P1.17.3.3
337
Feedback 1 minimum scale “FB 1 min scale”
This is the minimum percentage of source 1.
P1.17.3.4
338
Feedback 1 maximum scale “FB 1 max scale”
This is the maximum percentage of source 1.
P1.17.3.5
339
Feedback source 2“FB source 2”
This selects the Analog source of source 2.
P1.17.3.6
340
Feedback 2 minimum scale “FB 2 min scale”
This is the minimum percentage of source 2.
P1.17.3.7
341
Feedback 2 maximum scale “FB 2 max scale”
This is the maximum percentage of source 2.
5.18.4 Sleep
Code
ID
Description
Notes
P1.17.4.1
1016
Sleep frequency ID1016 “sleep frequency”
This defines the level where the PID controller will go tosleep when the output
frequency is below this level and hasexceeded the Sleep Delay time.
P1.17.4.2
119
PI controller I time “sleep delay”
This defines the level where the PID controller will goto sleep when the output
frequency is below The Sleepfrequency level and has exceeded this delay time.
P1.17.4.3
1018
Wake up limit ID1018 “PID reference”
When the Feedback value exceeds or is below this limitas defined by Wake up action.
The drive will start out ofsleep mode.
P1.17.4.4
1019
Wake up action “wake up action”
Sets if the sleep function will wake if above the wake up limit or below.