9. Problem solving
While proper information is needed form the problem, it’s also recommended to try with latest application- and system
software versions available. Software is continuously developed and default settings are improved.
Figure 2 . Recommended signals for 9000xdrive .
Use the fastest communication speed (Baudrate: 57 600)
and a 50 ms update interval for signals for the
RS232 communication.
For the CAN communication, use a 1 Mbit communication
speed and 7 ms update interval for signals.
When you contact the support, send the *.trn, *.par and
Service info (*.txt) files with a description of the situation. If
the situation is caused by a fault, take also the Datalogger
data from the drive.
Note that Datalogger settings can be changed to catch
correct situation and it’s also to possible make manual force
trig for Datalogger.
Before storing the parameter file, upload the parameters
from the drive and save when NCDrive is in the ON-LINE
state. If it is possible, do this while the problem is active.
It’s also helpful to have single line diagram from the system
where problem is faced.
Figure 3 . Data logger window opening and Service Info upload .