38
SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
4.12.7 Underload protection
Table 32 . Underload protection
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.12.7.1 Underload protection
0
3
0
713
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P1.12.7.2 Field weakening area load
10.0
150.0
%
50.0
714
P1.12.7.3 Zero frequency load
5.0
150.0
%
10.0
715
P1.12.7.4 Underload protection
time limit
2.00
600.00
s
20.00
716
4.12.8 Ground fault protection
Table 33 . Ground fault protection
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.12.8.1 Ground fault protection
0
3
2
703
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P1.12.8.2 Ground fault current limit
0.0
100.0
%
50.0
1333
4.12.9 Cooling protection
Table 34 . Cooling protection
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.12.9.1 Cooling fault response
1
2
2
762
0= No Action, warning
1= Warning, warning
2= Warning, fault
3= No action, fault
P1.12.9.2 Cooling fault delay
0.00
7.00
s
2.00
751
4.12.10 Fieldbus protection
Table 35 . Fieldbus protection
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.12.10.1 Fieldbus communication
response
0
5
2
733
0=No action
1=Warning
2= Fault
3= Fault,stop by coasting
4=Warning; Prev Freq
5=Quick Stop
P1.12.10.2 FB Fault delay
0.00
60.00
s
0.50
1850
Delay to fault when FB Response is 4
P1.12.10.3 FB watchdog delay
0.00
30.00
s
0.00
1354
Delay when WD pulse is missing. 0.00 s = Disabled
4.12.11 External fault
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.12.11.1 Response to external fault 1 0
3
2
701
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P1.12.11.2 Response to external fault 2 0
3
2
747
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting