5.19 Keypad control parameters
Unlike the parameters listed above, these parameters are
located in the M2 menu of the control keypad.
The reference parameters do not have an ID number.
Code
ID
Description
Notes
P2.1
125
Control place “control place”
The active control place can be changed with this parameter.
1 = Keypad L/R1
•
The keypad LOC/REM button will cycle between local and remote 1, A Force control
place input will override this setting
2 = Keypad L/R1/R2
•
The keypad LOC/REM button will cycle between local and remote 1 and remote 2, A
Force control place input will override this setting
3 = Local
•
Forces the control place to local and disabledforce inputs
4 = Remote 1
•
Forces the control place to Remote 1 and disabled force inputs
5 = Remote 2
•
Forces the control place to Remote 2 and disabled force inputs
6 = I/O Select
•
When no control place is selected with the force control place inputs the control place
is local. This disable the loc/rem Button on the keypad
R2.2
Keypad reference No ID “keypad reference”
The frequency reference can be adjusted from the keypadwith this parameter.The
output frequency can be copied as the keypadreference by pushing the Stop button for
3 seconds whenyou are on any of the pages of menu M2.
P2.3
123
Keypad direction “keypad direction”
0 Forward:
The rotation of the motor is forward, when the keypad is the active control place.
1 Reverse:
The rotation of the motor is reversed, when the keypad is the active control place.
P2.4
114
Stop button activated “StopButtonActive”
If you wish to make the Stop button a “hotspot” which always stops the drive
regardless of the selected control place, give this parameter the value 1.
R2.5
Torque reference no ID “torque reference”
Define here the torque reference within 0.0…100.0%.
R2.6
Power reference no ID “power reference”
Define here the power reference within 0.0…100.0%.
R2.7
PID reference 1 no ID “PID reference 1”
R2.8
PID reference 2 no ID “PID reference 2”
Define here the PID Reference in Engineering Units