SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P3.6.8.10
354
Drive temperature limit supervision function “temp lim superv.”
0 No supervision
1 Low limit supervision
2 High limit supervision
3 ABS(Torque), Low limit supervision
4 ABS(Torque), High limit supervision
The following five parameters are used to set a limit value to be monitored with the
corresponding parameter above.
P1.5.8.2
316
Output frequency limit supervision value “freq dupv val 1”
P1.5.8.4
347
Output frequency limit 2 supervision value “freq supv val 2”
P1.5.8.6
349
Torque limit, supervision value “torque supv val”
P1.5.8.9
351
Reference limit, supervision value “ref superv value”
P1.5.8.11
355
Drive temperature limit value “temp supv value”
Value
High
Lim
Low
Lim
Figure 5-11 . Supervision function
P1.5.8.7
402
Torque supervision value scaling input “torque superv scl”
This parameter is used to change the torque limit supervision level between zero and
P1.5.8.6 Torque Supv Val
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = A14
5 = FBLimScaling
5.5.4.1 Analog input supervision function
The analog input supervision function will control the
selected digital output to close when the analog input
Code
ID
Parameter
Notes
P1.5.8.12
356
Analog input supervision signal “ain supv input”
With this parameter you can select the analog input to be monitored.
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = FBLimScaling
signal has exceeded the high limit and open when the
signal goes below the low limit.