SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
5.15.2 DIN ID control
This function is used to control any parameter between
two different values with a digital input. Different values are
given for DI ‘low’ and DI ‘high’.
Code
ID
Description
Notes
P1.14.2.1
1570
ID control digital input “ID control DIN”
P1.14.3.1
1590
ID control digital input “ID control DIN”
P1.14.4.1
1578
ID control digital input “ID control DIN”
Select digital input to be used for controlling the parameter selected by ID1571, ID1575
and 1579.
P1.14.2.2
1571
DIN controlled ID ID1571 “controlled ID”
P1.14.3.2
1575
DIN controlled ID “controlled ID”
P1.14.4.2
1579
DIN controlled ID “controlled ID”
Select parameter ID controlled by ID1570.
P1.14.2.3
1572
Value for low digital input (FALSE) “false value”
P1.14.3.3
1592
Value for low digital input (FALSE) “false value”
P1.14.4.3
1594
Value for low digital input (FALSE) “false value”
Set here the controlled parameter value when the digital input (ID1570) is LOW for
the parameter selected by ID1571. The function does not recognize decimals. Give,
therefore, e.g. 10.00 Hz as ‘1000’.
P1.14.2.4
1573
Value for high digital input (TRUE) “true value”
P1.14.3.4
1593
Value for high digital input (TRUE) “true value”
P1.14.4.4
1596
Value for high digital input (TRUE) “true value”
Set here the controlled parameter value when the digital input (ID1570) is HIGH for
the parameter selected by ID1571. The function does not recognize decimals. Give,
therefore, e.g. 10.00 Hz as ‘1000’.
IN
IN
G
DIN Controlled ID
1
0
SEL
P
ID Control Digital Input
Value for LOW
Value for High
P
P
DI
5.15.3 ID-controlled DO
This function is used to control any Digital output by
anystatus that can be presented as bit.The input signal is
selected with the ID number and bit number.Example: Most
of the faults and warnings are normallypresented in the
common digital output. With theID-controlled DO function,
it is possible to select a specificfault to be connected to the
digital output.
Warning word 1 ID1174
Fault
Comment
b0
Motor stalled
W15
b1
Motor over temperature
W16
b2
Motor under load
W17
b3
Input phase loss
W10
b4
Output phase loss
W11
b5
Safe disable
W30 (Not implemented)
b6
FieldBus communication fault in slot D
W53 (Not implemented)
b7
FieldBus communication fault in slot E
W67 (Not implemented)
b8
Drive over temperature
W14
b9
Analog input < 4mA
W50
b10
Not used
b11
Emergency stop
W63 (Not implemented)
b12
Run disabled
W62 (Not implemented)
b13
Not used
b14
Mechanical brake
W58
b15
Not used