166
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
8.3.2 Status word combination 3, ByPass – basic
Most of the field busses use “MCStatus” as Status word that
is shown below. For profibus it can be selected what is the
status word, default is Combination 2 Status Word, ProfiDrive
type ID68 V7.3.2 MainStatusWord. Below Status Word can be
selected with P1.10.17 GSW Data by setting it to ID64
Main status word for profibus in combination 3
False
True
Comment
b0
Not ready
READY
b1
STOP
RUN
b2
Clockwise
Counter clockwise
b3
NO FAULT
FAULT ACTIVE
b4
No warning
Warning
b5
Reference ≠ Actual value
Reference = Actual value
b6
Speed > Zero
At zero speed
b7
Flux not ready
Flux ready
b8
TC Speed limit active
TC Speed limit not active
b9
Detected encoder direction clockwise
Encoder direction counter clockwise
b10
UV Fast stop active
UV Fast stop not active
b11
Not used
Not used
b12
Not used
Not used
b13
Not used
Not used
b14
Not used
Not used
b15
Not used
Not used
SM = Profibus board state machine