Installation
Eaton ePDU G3 Operation Manual P-164000277—Rev 5
23
5.
ePDU away from the rail (offset).
Position and lock two cage nuts far enough apart to stabilize the top
and bottom of the ePDU when mounted on the rail. Insert the cage nuts into the square rail hole with a
flat-blade screwdriver.
6.
Locate the two clip feet and four M6 screws (supplied). Turn the straight part of the bracket 90° (see
Figure 20).
7.
Position one mounting clip foot at a cage nut and secure the mounting clip foot to the rail with a screw.
Repeat for the second mounting clip. Tighten the screws.
Figure 20. Attaching the Rotated Clip to the Rail
8.
Snap the ePDU into the mounting clip feet. When you hear a clicking sound for each mounting clip foot,
the ePDU is secure.
9.
Continue to “Grounding the ePDU” on page 28 if you are installing a ground screw and grounding cable.
Otherwise, go to “Network and Environmental Ports” on page 29.
Using Mounting Brackets for Cisco Racks (US only)
To install the ePDU in a Cisco rack using mounting brackets:
1.
For each ePDU you will install, locate two mounting brackets with screws and keps nuts, and two clip feet.
2.
Decide the orientation in which you will mount the ePDU or ePDUs and install the clip feet to the bracket
as illustrated in the following figures:
l
One ePDU or Side-by-side inboard.
Outlets facing toward the other side of the rack, go to Figure 21
l
Multiple (up to four) 904 mm ePDUs inboard.
Outlets facing toward the other side of the rack, go to
l
One ePDU rearward
. Outlets facing out the back of the rack, go to Figure 23 on page 26.
3.
Position the brackets to align with the top, upper, lower, and/or bottom mounting rail.
NOTE
Mount the bracket with the clip feet facing up for upper and top rail installation.
Mount the bracket with the clip feet facing down for lower and bottom rail
installation.