LCD Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 5
60
Figure 64. Example Save eNMC File
Figure 65. Verify HW File at USB Root
5.
When the file is saved, click OK to confirm.
Load the ePDU Hardware Configuration File from the USB to the eNMC Module
See “Replacing the ePDU Network Management and Control Module” on page 117 to understand this
selection in proper context.This procedure is used as part of the replacement procedure.
The ePDU hardware configuration file provides the replacement eNMC module with the characteristics of the
ePDU model in which it resides, such as the type of input, the number of circuit breakers and outlets, and the
way measurements should be displayed. Use this menu selection to upload the ePDU model-specific hardware
configuration file to the replacement eNMC module.
To load the ePDU model-specific hardware configuration file to an eNMC module:
1.
Make sure the eNMC module is powered ON. Connect the USB flash drive to the ePDU with the new
eNMC module.
2.
When the LCD interface pop-up confirms that the USB flash drive is detected, click
OK
, then press
Enter
to return to the Main Menu. (If not confirmed within 10 seconds, the pop-up goes away by itself.)
3.
From the LCD Settings menu, select USB Flash Mode. Press Enter, select yes to confirm, and then press
Enter again. The module restarts. (If there is no action within one minute, the eNMC module exits USB
Flash Mode. Remove and reinsert the USB flash drive to access this menu again.)
4.
Select Load eNMC file, then click
OK
to upload the ePDU hardware configuration file to the eNMC (see
5.
When the file is successfully loaded, click
OK
to confirm.
6.
Remove the USB flash drive and select
Exit
.
NOTE
This selection will only display in the menu if an ePDU hardware configuration file is
detected on the USB drive.
Daisy Chain
Settings
LCD
IPv4
Factory
Display
Language
ESC
Enter
Main Menu
Active Alarms
Alarms History
Meters
Control
ePDU Info
Main Menu
Settings
Enter
ESC
USB Flash Mode
Main Menu
.
Upgrade F/W
Load eNMC file
Exit
USB Flash Mode
Save Config
.
Load Config
Save eNMC file