Installation
Eaton ePDU G3 Operation Manual P-164000277—Rev 5
19
Figure 15. Plug Retention Mechanism
Installing Vertical ePDUs in a Rack Cabinet
Regardless of the configuration you choose, there are three mounting methods available for installing the ePDU
vertically in a rack cabinet:
l
Using factory-installed buttons on the ePDU to mount the ePDU in keyhole openings in the rack frame
l
Using buttons on clip feet to mount the ePDU in keyhole openings in the rack frame
l
Using clip feet and cage nuts secured to the rack to mount the ePDU onto the clip
Review the installation methods described in this section and choose the method appropriate for your
environment.
Using Factory-installed Mounting Buttons
To install the ePDU with mounting buttons directly attached to the ePDU:
1.
Carefully move the ePDU into position against the rail.
2.
Insert the top and bottom mounting buttons into the keyhole slots on the rack post that correspond with
the position of the top and bottom mounting buttons.
3.
Does the factory-installed mounting button fit flush in the rack keyhole?
l
If no, go to Step 4.
l
If yes, go to Step 5.
4.
Unscrew and remove the mounting button. Turn it around 180°. Secure the mounting button to the ePDU
(see Figure 16).
NOTE
Only unplug the power cord when the grip plug retention mechanism is in the “+”
position in the event of an emergency.
NOTE
If you choose, you can further secure the plug with a cable tie.
NOTE
If you need to remove the ePDU from clip feet, hold on to the ePDU and use a flat
screwdriver to unsnap it from the clip.