Web Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 5
110
3.
The current Energy Wise state value displays in the Status field. Valid states are:
l
Unknown
l
Not Initialized
l
Stopped
l
Stopping
l
Starting
l
Started
l
Down
l
Initializing
l
Up
l
Active
l
Requested Shutdown
4.
For Command, select one of the following from the drop-down list:
l
Start
l
Graceful Stop
l
Off-State Cache Stop
l
Restart
5.
Click
Save
.
Security
Enable/Disable SSL Encryption
1.
Access the Web interface and log in.
2.
Under Network and Security, select Global. The Security page displays.
3.
In the Ports Settings panel, ensure that the
HTTP Enable
check box is checked and that the associated
HTTP Port number displays.
4.
Check the
Force SSL
check box to enable SSL encryption, or uncheck the box to disable it. If enabled, the
HTTPS Port entry box is active. Type the port number.
5.
Click
Save
.
6.
Open the System submenu in the Settings menu. In the Network Management Card panel, click
Restart
network management card
to restart the ePDU Network Management and Control (eNMC) module.
NOTE
With SSL encryption, the Web interface is accessible from
https://<IPv4 address>
and the
https://[IPv6 address]
, or both, according to the IP configuration.
NOTE
When
Force SSL
is selected, the Web page is only available through HTTPS. If you
enter the IP address through HTTP, it will be automatically redirected to HTTPS and
you will receive the following message and a new URL link:
The Network Management Card is protected by SSL encryption.
Please use the following address(es) to connect to the Network
Management Card. https://166.99.224.82