![Eaton ePDU G3 Operating Manual Download Page 49](http://html.mh-extra.com/html/eaton/epdu-g3/epdu-g3_operating-manual_524483049.webp)
Operation Overview
Eaton ePDU G3 Operation Manual P-164000277—Rev 5
40
!
IMPORTANT
To power cycle the Eaton ePDU, remove the power cord from the power source and then plug it
back in.
Shutting Down the ePDU
To shut down the ePDU:
1.
Shut down the connected devices according to the manufacturer’s recommended shutdown sequence.
2.
Turn each circuit breaker to the Off position.
3.
To remove power from the ePDU completely, disconnect the ePDU power cord from the power source.
Restarting the ePDU Network Management and Control (eNMC) module
You can restart the communications module using either a hardware or software method.
!
IMPORTANT
Restarting the eNMC module will not affect the output power or the connected equipment.
A software restart is triggered from the Serial interface or Web interface upon user action (see Figure 36). This
method is typically the better choice because all current settings in the communications module file system are
saved before restarting.