3 Installation
3.3 Flush mounting in control panel
70
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
3.3.2.2 Fitting on mounting plate
The DS7 soft starters are screwed onto the switch cabinet wall (mounting
plate). The control signal terminals and the operator control and display
elements must face the front. The screw fixing is completed with at least
two diagonally arranged flat head screws. The use of washers and split
washers is recommended.
Figure 51: Screw fixing on mounting plate (example using size 1)
Size 1 (up to 12 A)
Size 2 (up to 32 A)
Figure 52: Drilling dimensions
⌀
4.2 mm
(0.17")
l ≧
16 mm
(l ≧ 0.63")
2 x M4
1.3 Nm
(11.50 lb-in)
4 x M4
122 mm
35 mm
(4.8")
(1.38")
2 x M4
140 mm
35 mm
(1.38")
(5.51")