8 SmartWire-DT
8.9 Programming
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
207
SmartWire-DT read re) – Without data
As soon as the DS7-SWD soft starter has completed the response for a write
job, it will send a SmartWire-DT read re) – without data.
SmartWire-DT read re) – With data (all PNUs)
As soon as the DS7-SWD soft starter has completed the response for a read
job for the range PNU 0 – PNU 999 (without PNU 202), it will send a
SmartWire-DT read re) – with data.
SmartWire-DT read re) – With data (PNU 202)
As soon as the DS7-SWD soft starter has completed the response for a
PNU 202 read job, it will send a SmartWire-DT read re) – with data.
Byte
Designation
Description
0
Request Reference
Request identification: Is echoed
1
Response-ID
Response ID: 02
hex
: Write job (+)
2
DO-ID
Drive-Object-ID: Is echoed
3
No. of Parameters
Number of Parameters: 01
hex
Byte
Designation
Description
0
Request Reference
Request identification: Is echoed
1
Response-ID
Response ID: 01
hex
: Read job (+)
2
DO-ID
Drive-Object-ID: Is echoed
3
No. of Parameters
Number of Parameters: 01
hex
4
Format
Format: 01
hex
– 7C
hex
(i.e. 01
dec
– 124
dec
)
5
No. of Values
Number of values: 01
hex
: value
6 - 9
Value
Value: Specifies the value of the parameter being accessed.
The length depends on the format and can be a maximum of 4 bytes.
00000000
hex
- FFFFFFFF
hex
(i. e. 0
dec
- 4294967295
dec
)
Content of PNU 0 – PNU 999 (without PNU 202)
Byte
Designation
Description
0
Request Reference
Request identification: Is echoed
1
Response-ID
Response ID: 01
hex
: Read job (+)
2
DO-ID
Drive-Object-ID: Is echoed
3
No. of Parameters
Number of Parameters: 01
hex
4
Format
Format: 0A
hex
(= 10
dec
)
5
No. of Values
Number of values: 01
hex
: value
6 - 25
Value
Value: Specifies the value of the parameter being accessed.
The length depends on the format and can be a maximum of 20 bytes.
Content of PNU 202
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...