8 SmartWire-DT
8.9 Programming
194
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
Fire Mode
In normal operation each error message causes the soft starter to switch off.
If Fire mode is active, all protective functions can be disabled. In this case,
the soft starter will continue to run until it is ruined. Fire mode can be
activated by setting the error response to a value of “No response.”
Use parameter PNU 840 to do so. All the corresponding subindexes must be
set to 0.
The seven most recent faults will be stored in the device.
→
Fire mode can only be used when using profile 7, 8, 9, or 11.
In addition, bus monitoring must be enabled.
DANGER
Having Fire mode enabled will pose a risk of serious injury,
death, and property damage, as it will no longer be possible to
control the soft starter and the soft starter will remain active.
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...