4 Operation
4.4 Potentiometer settings
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
103
Figure 74: Recommended settings per application
~18
~40
0
J
l
L
High flywheel mass
a
Soft starter DS7
should have a higher
output than the
assigned motor.
~15
~50
0
Tunnel fan
Axial fan
a
Soft starter DS7
should have a higher
output than the
assigned motor.
~10
~60
0
Bulk conveyor
Escalator
~10
~60
0
Mixers
Agitators
a
Soft starter DS7
should have a higher
output than the
assigned motor.
→
When using DS7-SWD soft starters, these settings can be
adjusted using parameters (PNU) (
DS7 soft starter data”, page 186.
t-Start [s]
U-Start [%]
t-Stop [s]
Application example
t-Start (s)
U-Start (%)
t-Stop (s)
30
1
20
10
100
30
30
0
20
10
30
1
20
10
100
30
30
0
20
10
30
1
20
10
100
30
30
0
20
10
30
1
20
10
100
30
30
0
20
10