8 SmartWire-DT
8.9 Programming
154
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
8.9.2.8 Network – State diagram for profiles 7, 8, 9, 11
If profile 7, 8, 9, or 11 (
Long
) is used with
PNU 928.0 = 1
, the state diagram
shown below will apply.
Figure 121: State diagram: Network (profiles 7, 8, 9, 11)
→
In addition to the transition conditions shown below, the
Ctl_PLC bit needs to be set in the output byte.
→
For more information on the Ctl_Req and Ctl_PLC bits, see
S1: Switching On Inhibited
Bit 6 = 1; Bit 0, 1, 2 = 0
S2: Ready For Switching On
Bit 0 = 1; Bit 1, 2, 6 = 0
S3: Switched On
Bit 0, 1 = 1; Bit 2, 6 = 0
S4: Operation
Bit 0, 1, 2 = 1; Bit 6 = 0
Standstill or
Bit 3 = 0
(EN_Op)
Standstill or
Bit 3 = 0
(EN_Op)
Bit 0 = 0 (OnOff) and
Bit 1 = 1 (Off2) and
Bit 2 = 1 (Off3)
S5: Switching Off
(Quick Stop)
Bit 0, 1, 5 = 1; Bit 2, 6 = 0
S5: Switching Off
(Ramp Stop)
Bit 0, 1 = 1; Bit 2, 5, 6 = 0
Bit 2 = 0 (Off3)
Bit 0 = 1 (OnOff)
Bit 0 = 0 (OnOff)
Bit 1 = 0
(Off2)
Bit 1 = 0
(Off2)
Bit 3 = 1
(EN_Op)
Bit 3 = 0
(EN_Op)
Bit 0 = 1
(OnOff)
Bit 0 = 0
(OnOff)
Bit 2 = 0
(Off3)
Bit 2 = 0
(Off3)
Bit 1 = 0
(Off2)
Power supply on
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...