2.9 DS7-SWD and PKE motor-protective circuit-breakers
DS7-SWD soft starters can also provide the following functions when used
together with a PKE motor-protective circuit-breaker:
•
Protecting the DS7 soft starter against overload
•
adjustable current limitation,
•
ZMR overload relay function (in the event of an overload, the DS7 soft
starter will switch off the load, instead of the PKE motor-protective
circuit-breaker doing so)
•
Currents readable via SmartWire-DT
→
After a motor protective device has tripped, the soft starter and
the protective device cannot be switched on again until it has
cooled down. The reset depends on the temperature.
Figure 21: Motor-starter combination: DS7-SWD and PKE
→
Only PKE trip blocks (PKE-XTUWA-32, PKE-XTUA-…) should be
used for motor protection in combination with DS7 soft starters.
PKE trip block PKE-XTUCP-… for system protection must not be
used in combination with a soft starter DS7! In combination
with SmartWire-DT this can cause false tripping.
M
3 ~
1L1
3L2
5L3
2T1
4T2
6T3
L1
L2
L3
PE
Q1
Q21
BG1, BG2
M1
I > I > I >
SWD4-8SF2-5
+ 15V
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...