2 Engineering
2.11 Motor connection
48
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
2.11.9 Cascade circuit
The DS7 soft starters can be used to start several motors in sequence.
This requires the observance of a specific switching sequence (
2.11.10 Motors with power factor correction capacitor
If capacitors are to be used for power factor correction and thus to improve
the power factor, they must be connected to the mains side of the soft
starter.
The following Figure 31 shows on the right a safe arrangement.
During the startup and stop phase (generalized phase control), the power
factor correction capacitors are disconnected. After the start time (t-Start)
elapses, they are connected via the TOR signal of the soft starter and the
capacitor contactor Q12, which disconnect them at the beginning of the stop
time (t-Stop).
Figure 31: Reactive current compensated motor
Left: impermissible connection;
Right: permissible connection
→
When starting several motors with one soft starter the thermal
load of the soft starter (starting frequency, current load) must be
taken into account.
If the starts occur closely in succession, the soft starter must be
dimensioned larger (i.e. the soft starter must be designed with
an accordingly higher load cycle).
→
In networks with electronically controlled consumers (e.g. soft
starters), the compensation devices must always be connected
with a series inductance.
M
M1
3
Q11
Q21
L1
L2
L3
Q1
L1 L2 L3
T1 T2 T3
M
M1
3
Q11
Q21
L1
L2
L3
Q12
TOR
Q1
L1 L2 L3
T1 T2 T3
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...