2 Engineering
2.7 Residual current circuit-breaker (RCD)
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
37
2.7 Residual current circuit-breaker (RCD)
Residual current circuit-breakers – also referred to as RCDs (residual current
devices) and ground fault circuit interrupters (GFCIs) – protect people and
livestock from the presence (not the production!) of impermissibly high
touch voltages. They prevent dangerous and fatal injuries caused by
electrical accidents and also serve as fire prevention.
Size 1 and 2 soft starters of the DS7 series have no connection to the earth
potential (PE). In size 3 and 4, the DS7 soft starters have an exposed heat
sink which must be connected with the earth potential (PE).
When using a DS7 soft starter, there is no leakage current at the motor
feeder. Standard residual current circuit breakers (RCD part no. A) up to
30 mA can be used.
Figure 19: Motor feeder with RCD
F1 = Residual current circuit breaker (RCD)
F3 = optional semiconductor fuse
Q1 = Cable prot motor protection
Q21 = Soft starter
M1 = Motor
M
3 ~
1L
1
2L
3
3L
5
1T
2
2T
4
3T
6
L1
L2
L3
PE
Q1
RCD
Q21
BG1, BG2
F1
F3
M1
I > I > I >
1L
1
2L
3
3L
5
1T
2
2T
4
3T
6
BG3, BG4
PE
PE
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...