8 SmartWire-DT
8.9 Programming
200
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
8.9.6.4 SmartWire-DT write request – Write job
Only individual parameter writing is supported (i.e., array and multiple
parameter writing is not supported). The maximum parameter request frame
length is set at 16 bytes. The maximum length of a writable parameter is one
double word. All kinds of objects can be transmitted in the parameter
channel – these objects are identified by what is referred to as a PNU
(parameter number) and a subindex. The write request includes a declaration
that specifies that the job is a write job.
The valid formats (byte 10) for the DS7-SWD soft starter from PROFIdrive
profile are marked in the following table:
Byte
Designation
Description
0
Request Reference
Request identification:
Unique identification for a request/response pair for the master.
The master can increment the identification number for each new
request in the application. The DS7-SWD will then echo it.
01
hex
- FF
hex
(i.e. 1
dec
- 255
dec
)
1
Request ID
Request ID:
The type of request is specified here.
02
hex
: Write job
2
DO-ID
Drive-Object-ID:
00
hex
3
No. of Paramters
Number of parameters:
Only individual parameter processing is supported.
01
hex
4
Attribute
Attribute:
Defines which object type should be accessed.
10
hex
(16
dec
): Value
5
No. of Elements
Number of elements:
Address of the parameter that should be accessed
PNU 0 - PNU 999: 00
hex
(for subindex 0 only)
PNU 0 - PNU 999: 01
hex
6, 7
Parameter number
Parameter number (PNU):
Address of the parameter that should be accessed
0000
hex
- FFFF
hex
(i.e. 0
dec
- 65535
dec
)
8, 9
Subindex
Subindex:
Address of the parameter’s first field element or start of the text
0000
hex
- FFFF
hex
(i.e. 0
dec
- 65535
dec
)
10
Format
Format:
01
hex
- 7C
hex
(
→
01
dec
- 124
dec
)
11
No. of Values
Number of values being accessed.
01
hex
12 - (15)
Value
Value: Specifies the value of the parameter being accessed.
The length depends on the format and can be a maximum of 4 bytes.
00000000
hex
- FFFFFFFF
hex
(i. e. 0
dec
- 4294967295
dec
)
→
In this case, the number of bytes is variable (13, 14, or 16) and
will depend on the selected format.
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...