8 SmartWire-DT
8.9 Programming
190
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
860
0
ro
Warnings
Unsigned32
Warnings
If bit WARN = 1 in profiles 7, 8, 9,
11, a warning is active. The
warning can be read in PNU 860.0.
Reading the warning will only be
possible as long as the warning is
active. Warning bits 16 to 24 will
only be generated if the error
response for the corresponding
fault is (PNU 840.X) = 1.
Example: PNU 860.0: Bit 20 = 1
→
Thyristor fault
2
0
:
NoCurrentFeedback
(generated if current limiting
(PNU 681.0) is activated and the
DS7-SWD soft starter has the
RUN status.)
2
1
:
OvertempForNextStart (the
heat sink is still too hot for a new
start; however, continuous
operation can be continued.)
2
2
: StartWithoutEnable (start
command active, but no EN signal
present yet)
2
16
: HeatsinkOverUnderTemp
(Heat sink overtemperature/
undertemperature)
2
17
: ElectronicsOverTemp
(Overtemperature Electronic)
2
18
: ThyristorOverTemp
(Overtemperature, thyristor (I
2
t))
2
19
: SupplyVoltageFault (Supply
voltage error)
2
20
: ThyristorFault (Thyristor error)
2
21
: BypassDefective (Bypass is
defective)
2
22
: PhaseLoss (phase failure)
2
23
: CommunicationFault
(erroneous communication)
2
24
: ExternalFault (external fault)
0 - 4294967295
PNU
Index
PNU
Sub-
index
Access
rights
Designation
Data type
Meaning
Value range
DS
User
setting
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...