2.4 Power connection
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
35
2.4 Power connection
The power section should be protected according to the connection form
used.
Cable and device protection on the supply side:
•
Input AC… via standard fuses for cable protection or via motor-protective
circuit-breaker.
•
Fuses in UL compliant systems must be UL-approved.
•
The rated operating voltages of the fuses must be suitable for the local
mains voltage.
•
No fuses are required on the motor side.
The following figure shows the basic connection of motor and power
section.
Figure 18: Connecting the power section and motor
F3 = optional semiconductor fuse
Q1 = Cable prot motor protection
Q21 = Soft starter
M1 = Motor
At the output of the soft starter (terminals 2T1, 4T2, 6T3) you must not
•
Connect any capacitive load (e.g. phase compensation capacitors),
•
Connect several soft starters in parallel,
•
Feed a mains voltage or a voltage from a variable frequency drive or other
voltage source.
M
3 ~
1L
1
2L
3
3L
5
1T
2
2T
4
3T
6
L1
L2
L3
PE
Q1
Q21
F3
M1
I > I > I >
≦ 32 A
1L
1
2L
3
3L
5
EP
EP
1T
2
2T
4
3T
6
Q21
≧ 41 A
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...