8 SmartWire-DT
8.9 Programming
178
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
8.9.3.10 Profile 10: Inputs (status)
Input bytes 0 and 1 (Short) are mapped as follows on SmartWire-DT.
Table 36: Profile 10: Input bytes 0 and 1
Byte
Bit
Designation
Meaning
0
0, 1
–
Not used
2, 3
A1, A2
1-0-A switch on DS7:
00: not defined
10: Position A: Automatic (commands via
SmartWire-DT/control signal terminal)
01: Position 0: DS7 stop
11: Position 1: DS7 operation
4
DIAG
0: no diagnostic alarm
1: Diagnostic alarm present
5
–
Not used
6
PRSNT
0: Device not present
1: Device present
7
SUBST
0: Configured module present
1: universal module M22-SWD-NOP(C) present
1
0
ERR
Error present
0: no error
1: Error
1
WARN
Warning present:
0: no warning
1: Warning
2
RDY
Ready to operate, switched on
0: not switched on
1: switched on
3
RUN
DS7 running, power section active
(DS7 Run, power part active):
0: Stop (power section inactive)
1: Operation (power section active)
4
TOR
Top of ramp:
0: Top of start ramp not reached
1: Top of start ramp reached
5
1)
CL
Current limit:
0: Current limit not reached
1: Current limit reached
6, 7
–
Not used
1) Bit 5 will only be activated if parameter 681.0 is set to 1.
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...