8 SmartWire-DT
8.9 Programming
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
187
210
0
rw
I
m
Unsigned16
Rated motor current I
m
from
nameplate:
X = I
m
x 10
X = Read/written value
Example:
Rated motor current: 2, 3 A
Value that the PLC needs to send:
23
The value is used to calculate the
current limit (PNU 281.1).
It must be sent by the PLC if it is
different from the DS7’s rated
operational current I
e
. (I
e
is used
as a default setting.)
0 - 65535
0
280
0
ro
I
e
Unsigned16
Soft starter rated operational
current I
e
:
X = I
e
x 10
X = Value read here
0 - 200
–
281
1
rw
CurrentLimit
Unsigned16
Current limitation:
A current limitation can be
implemented here by using a PKE.
If the configured limit value is
reached, the DS7-SWD will freeze
the voltage ramp and set the CL bit
in the SWD input byte (profiles 7,
to 9, and 11). PNU 681.0 activates
and deactivates the current
limitation. If the PKE does not
deliver any current, but PNU 681.0
= 1 and the DS7-SWD is running,
the DIAG2 bit will be set and, in
profiles 4 to 11, the WARN bit will
be set as well.
Rated motor current I
m
(PNU
210.0) is used for calculating the
current limitation within this
context. The value is independent
from the PKE motor-protective
circuit-breaker and from the DS7-
SWD soft starter model.
0 - 800 %
65535
300 %
24576
290
0
ro
rw
(version
V48 and
higher)
IeBreakerMax
Unsigned16
Maximum current of PKE:
X = I
e
Breaker x 10
X = Value read here
I
e
= 21.7 A; X = 217
0 - 650
0
310
0
ro
Profiles
Unsigned16
Profile group being used
0: No selection
10: PROFIdrive profile
(Profiles 7, 8, 9, 11)
11: Short profile
(Profiles 4, 5, 6, 10)
12: Motor starter profile
(Profiles 1, 2, 3)
0 - 12
10
PNU
Index
PNU
Sub-
index
Access
rights
Designation
Data type
Meaning
Value range
DS
User
setting
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...