8 SmartWire-DT
8.9 Programming
186
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
8.9.5.2 Acyclic DS7 soft starter data
The following table lists the various available parameters (PNUs). These
parameters are transmitted via the parameter channel described in the
following section.
PNU
Index
PNU
Sub-
index
Access
rights
Designation
Data type
Meaning
Value range
DS
User
setting
Manufacturer Specific
11
0
rw
U-Start
N2
Start voltage
30 - 100 %
4915 - 16384
30 %
4915
11
1
ro
U-StartPoti
N2
Start voltage via potentiometer.
If local device control
(PNU 928=0), this value will
overwrite PNU 11.0.
30 - 100 %
4915 - 11468
4915
12
0
rw
U-StartEnd
N2
U-start-end: The maximum ramp
voltage is reproduced here as a
percentage. Maximum reached:
100 %
30 - 100 %
4915 - 16384
100 %
16384
13
0
rw
U-StopStart
N2
U-stop-start: In the event of a soft
stop, the voltage will fall down to
the value set here; the stop ramp
will start
30 - 100 %
4915 - 16384
100 %
16384
14
0
rw
U-Stop
N2
U-Stop: Minimum ramp voltage
(end of soft stop), minimum
reached = 0 %
30 - 100 %
4915 - 16384
30 %
4915
111
0
rw
t-Start
T2
Start time
1 - 30 s
10 - 300
5 s
50
111
1
ro
t-Start-Poti
T2
Start time via potentiometer.
If local device control
(PNU 928=0), this value will
overwrite PNU 111.0.
1 - 30 s
10 - 300
–
112
0
rw
TOR-Delay
D2
Time between top of ramp and
TOR bit
150 - 400 ms
24576 - 65535
150 ms
24576
113
0
rw
Stop-Delay
D2
Stop delay:
Time between TOR and start of
stop ramp
150 - 400 ms
24576 - 65535
150 ms
24576
114
0
rw
t-Stop
T2
Stop Time
0 - 30 s
0 - 300
0 s
0
114
1
ro
t-StopPoti
T2
Stop time via potentiometer.
If local device control
(PNU 928=0), this value will
overwrite PNU 114.0.
0 - 30 s
0 - 300
–
202
0
ro
Device Name
OctetString
DS7 designation
–
–
203
0
ro
HW version
Unsigned16
Hardware Version
0 - 65535
0
206
0
ro
Firmware Version
(DS7-SWD)
Unsigned16
Firmware Version
(DS7-SWD)
0 - 65535
–
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...