IL17569C
Page 4-16
FP-5000
Effective Date: 12/05
Page 4-16
For more information visit:
www.eatonelectrical.com
Effective Date: 12/05
“Alarms” Display:
50P-3 PH IOC Alarm
Pickup: Disable
Delay (c): 0
Direction: Both
46-2 I Unbal Alarm
Threshold: 0.10
% Unbal (I2/I1): 40
Delay (c): 60
50R-3 IR IOC Alarm
Pickup: Disable
Delay (c): 0
Direction: Both
50X-3 IX IOC Alarm
Pickup: Disable
Delay (c): 0
Direction: Both
47-2 V Unbal Alarm
Threshold V: 50
% (V2/V1): 40
Delay (c): 60
Alarms
50P-3 PH IOC Alarm
50X-3 IX IOC Alarm
50R-3 IR IOC Alarm
46-2 I Unbal Alarm
47-2 V Unbal Alarm
59M-2 Over V Alarm
27M-2 Under V Alarm
59A-2 Over V Alarm
27A-2 Under V Alarm
59N-2 OV Definition
59N-2 OV Alarm
81O-2 Over Freq Alm
81U-2 Under Freq Al
32-3 Pwr Definition
32-3 Power Alarm
59M-2 Over V Alarm
Phase: Any One
Threshold V: Disable
Delay (c): 0
27M-2 Under V Alarm
Phase: Any One
Threshold V: Disable
Delay (c): 0
59A-2 Over V Alarm
Threshold: Disable
Delay (c): 0
27A-2 Under V Alarm
Threshold: Disable
Delay (c): 0
59N-2 OV Definition
Source: Calc
Criterion: Phasor
59N-2 OV Alarm
Threshold: Disable
Delay (c): 1200
81O-2 Over Freq Alm
Threshold: Disable
Delay (c): 0
81U-2 Under Freq Al
Threshold: Disable
Delay (c): 0
32-3 Pwr Definition
Direction: Reverse
Criterion: Over
32-3 Power Alarm
Threshold: Disable
Delay (c): 0