IL17569C
Page 5-20
FP-5000
Effective Date: 12/05
Page 5-20
For more information visit:
www.eatonelectrical.com
Effective Date: 12/05
Contact Input Configuration Settings
: Phase time overcurrent (51P) and instantaneous (50P-1 & 50P-2) device settings
Display Setting
Description
Setpoint Range/
Default
Selected
Refer to
Value Selection
Setting
Value
Sec. #
Contact input
Contact Input
5.5.5
CFG
Configuration Settings
9.1
Cin1:
Select Cin1 configuration
user defined, 52a, 52b,
52a
BFI, Bkr Trouble,
Cin2:
Select Cin2 configuration
Remote Open,
52b
Remote Close,
Cin3:
Select Cin3 configuration
Remote Reset,
BFI
Datalog Trigger,
Cin4:
Select Cin4 configuration
Demand Sync,
Bkr Trouble
Sync Bypass,
Cin5:
Select Cin5 configuration
Sync Block,
Remote
Select Set 1,
Open
Select Set 2
Cin6:
Select Cin6 configuration
Remote
Close
Cin7:
Select Cin7 configuration
Remote
Reset
Cin8:
Select Cin8 configuration
user
defined
Table 5.5 Contact Input Configuration Settings
Note:
The I/O Configuration Setting in the System Configuration settings menu must be set to “custom” for these
set points to be configured. Otherwise the default settings displayed are used. See sections 5.4.5 and 5.4.6 for
details.