VPR-126-2R

TECHNICAL SPECIFICATION

TERMINAL CONNECTION

MECHANICAL INSTALLATION

Page -1

VOLTAGE PROTECTION RELAY

NC

R2

R1

NC

C

C

NO

NO

V

SET

L

L3

VPR 126-2R

L1

R1

L2 L3

2 4 0

45

R2

N

L1

L2

N

Front View(mm)

110

75

75

Side View(mm)

L1

L

N

NC

R2

R1

NC

C

C

NO

NO

L2 L3 N

SET

VPR 126-2R

L1

R2

R1

L2 L3

V

R

Y

B

N

TO

LOAD

FEATURES :

INPUT SPECIFICATION :

DISPLAY AND KEY :

GENERAL SPECIFICATION :

Protection Available

3 digit bright LED display,   Auto/ Manual/ ZVR Reset Option

Time parameter: Power on delay, Trip delay 

Recovery time ( Auto Reset ) 

Over Voltage

Asymmetry

Over Frequency

Phase Sequence

Under Voltage

Phase Loss

Under Frequency

Direct Voltage AC 

Frequency 

Resolution  

Accuracy 

50 to 300V AC (L - N) 3Ø-4W/

 

1Ø-2W

85 to 520V AC (L - L) 3Ø-3W

45.0 Hz to 65.0 Hz  

Class 1.0  

Display

Dimension (mm) 

Keys

Trip Setting

3 digit, 1line, 7 seg, 0.4” RED LED

75 (H) x 45 (W) x 110 (D) mm

SET, INC, DEC/RST

1 Volt

Time Parameter

Power ON Delay Time : 0 To 99 Sec.

Trip delay Time : 0 To 999 Sec.
Recovery Time : 0 To 99 Sec.

Over Frequency : 45.0 Hz To 65.0 Hz

Under Frequency : 45.0 Hz To 65.0 Hz

Phase Asymmetry : 2-30%

Under Voltage : 85-520V AC 3Ø-3W
                 50-300V AC 3Ø-4W/1Ø-2W
Over Voltage : 85-550V AC 3Ø-3W
                 50-330V AC 3Ø4W/1Ø2W 

Network Selection  3Ø-3W/3Ø-4W/1Ø-2W

 

OUTPUT SPECIFICATION :

AUXILIARY SUPPLY :

Relay

Supply voltage

Relay Type

Power consumption
(VA RATING)

Rating

2 nos.

1  C/O (NO-C-NC)

3 VA @ 230V AC MAX

ENVIRONMENT CONDITION :

NETWORK CONNECTION :

Relative Humidity

Protection Level
(As per request)

 Operating Temp.

0°C to 55°C

UP to 95% RH 
(non-condensing)
IP-65 (Front side) As per IS/IEC
60529 : 2001

100 to 270V AC, 50-60Hz

st

1  Relay 10A, 230V AC

nd

2  Relay 5A, 230V AC

3Ø-3W/3Ø-4W/1Ø-2W

 

Class 1.0 (Standard)

ACCURACY