PARAMETER SETTING
Password
If over voltage is enable
If under voltage is enable
(Over Voltage Of Relay 1)
(Over Voltage value)
(Over Frequency Value)
(Under Frequency value)
(Under Voltage of Relay 1)
(Over Frequency of Relay 1)
p a s
7 3
O V1
2 8 0
2 8 0
O F 1
5 5 0
4 S S
U F 1
(
85-550V For 3Ø-3W )
(50-330V For 3Ø-4W/1Ø-2W
)
(Under Voltage Value)
If Over Frequency is Enable
If Under Frequency is Enable
(45.0-65.0 Hz)
If Over
Frequency
is Disable
(Under Frequency Of Relay 1)
(45.0-65.0 Hz)
If Under
Frequency
is Disable
A S 1
(Asymmetry Of Relay 1)
If Asymmetry is Enable
2 0
(Asymmetry Percentage)
(2 - 30%)
If
Asymmetry
is Disable
or
Press key for save & exit
SET
Press key
SET
Press key
SET
Press key
SET
u V 1
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Relay-1 Settings
If Over
Voltage
is Disable
If Under
Voltage
is Disable
Press key
for 5 sec
Enter Password 73
SET
Password 11
:
To Enable / Disable parameter
(Over Voltage, Under Voltage,over
Frequency,Under Frequency,
Asymmetry,Phass loss, Phase
sequence)
Password 37 :
To set Power on delay time, Trip delay
Time,Relay Fault Mode.
Press key
SET
(
85-520V For 3Ø-3W )
(50-300V For 3Ø-4W/1Ø-2W
)
IF 3Ø-4W/3Ø-3W Selected
IF 1Ø-2W
Selected
Password
Over Voltage
(Enable/Disable)
(Enable/Disable)
(Enable/Disable)
(Enable/Disable)
Press key for save & exit
(Under Frequency)
(Under Voltage)
(Over Frequency)
Press key
SET
SET
p a s
1 1
O V
e n b
u V
e n b
O F
e n b
e n b
u F
(Enable/Disable)
(Enable/Disable)
(Enable/Disable)
(Phase Sequence)
(Phase loss)
(Asymmetry)
a s
e n b
e n b
p L
p s
e n b
IF
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
for 5 sec
Enter Password 11
SET
1Ø-2W
Selected
1Ø-2W
Selected
IF